range of product |
TeSys D
TeSys F |
|
---|---|---|
range |
TeSys
|
|
product or component type |
Auxiliary contact block
|
|
auxiliary contacts operation |
Instantaneous
|
|
pole contact composition |
1 NO
|
|
connections - terminals |
Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - with cable end
Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - without cable end |
mounting location |
Front
|
|
---|---|---|
[Ui] rated insulation voltage |
690 V - conforming to IEC 60947-5-1
600 V - certifications CSA 600 V - certifications UL |
|
[Ue] rated operational voltage |
690 V AC 25...400 Hz
|
|
[Ith] conventional free air thermal current |
10 A at <= 60 °C
|
|
Irms rated making capacity |
140 A at <= 690 V AC conforming to IEC 60947-5-1
250 A at <= 690 V DC conforming to IEC 60947-5-1 |
|
permissible short-time rating |
100 A at 60 °C 1 s
120 A at 60 °C 500 ms 140 A at 60 °C 100 ms |
|
protection type |
GG fuse <= 10 A rating according to operational current for Ue <= 690 V
|
|
associated fuse rating |
10 A gG IEC 60947-5-1
|
|
mechanical durability |
30 Mcycles
|
|
minimum switching current |
5 mA
|
|
minimum switching voltage |
17 V
|
|
non-overlap time |
1.5 ms on de-energisation (no overlap between NC and NO contact)
1.5 ms on energisation (no overlap between NC and NO contact) |
|
overlap time |
1.5 ms
|
|
insulation resistance |
> 10 MOhm
|
|
product weight |
0.02 kg
|
environmental characteristic |
Normal environment
|
|
---|---|---|
standards |
BS 4794
EN 60947-5-1 IEC 60947-5-1 NF C 63-140 VDE 0660 |
|
product certifications |
CSA
UL |
|
IP degree of protection |
IP2x conforming to VDE 0106
|
|
protective treatment |
TH conforming to IEC 60068
|
|
ambient air temperature for operation |
-5...60 °C
|
|
ambient air temperature for storage |
-60...80 °C
|
|
operating altitude |
3000 m without derating in temperature
|
range of product |
TeSys D TeSys F |
|
---|---|---|
range | TeSys | |
product or component type | Auxiliary contact block | |
auxiliary contacts operation | Instantaneous | |
pole contact composition | 1 NO | |
connections - terminals |
Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - without cable end |
mounting location | Front | |
---|---|---|
[Ui] rated insulation voltage |
690 V - conforming to IEC 60947-5-1 600 V - certifications CSA 600 V - certifications UL |
|
[Ue] rated operational voltage | 690 V AC 25...400 Hz | |
[Ith] conventional free air thermal current | 10 A at <= 60 °C | |
Irms rated making capacity |
140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1 |
|
permissible short-time rating |
100 A at 60 °C 1 s 120 A at 60 °C 500 ms 140 A at 60 °C 100 ms |
|
protection type | GG fuse <= 10 A rating according to operational current for Ue <= 690 V | |
associated fuse rating | 10 A gG IEC 60947-5-1 | |
mechanical durability | 30 Mcycles | |
minimum switching current | 5 mA | |
minimum switching voltage | 17 V | |
non-overlap time |
1.5 ms on de-energisation (no overlap between NC and NO contact) 1.5 ms on energisation (no overlap between NC and NO contact) |
|
overlap time | 1.5 ms | |
insulation resistance | > 10 MOhm | |
product weight | 0.02 kg |
environmental characteristic | Normal environment | |
---|---|---|
standards |
BS 4794 EN 60947-5-1 IEC 60947-5-1 NF C 63-140 VDE 0660 |
|
product certifications |
CSA UL |
|
IP degree of protection | IP2x conforming to VDE 0106 | |
protective treatment | TH conforming to IEC 60068 | |
ambient air temperature for operation | -5...60 °C | |
ambient air temperature for storage | -60...80 °C | |
operating altitude | 3000 m without derating in temperature |