140ACO13000
ANALOG OUT 8 CHAN CURRENT
| range of product |
Modicon Quantum automation platform
|
|
|---|---|---|
| product or component type |
Analogue output module
|
| analogue output number |
8
|
|
|---|---|---|
| addressing requirement |
8 output words
|
|
| loop voltage |
6...30 V DC
|
|
| voltage drop |
30 V 25 mA
|
|
| analogue output range |
0...20 mA 0...20000 counts
0...25 mA 0...25000 counts 4...20 mA 0...16000 counts 4...20 mA 0...4095 counts |
|
| absolute accuracy error |
+/- 0.2 % of full scale at 25 °C
|
|
| linearity |
+/- 12 µA 4...20 mA 0...4095 counts
+/- 4 µA 0...20 mA 0...20000 counts +/- 4 µA 0...25 mA 0...25000 counts +/- 4 µA 4...20 mA 0...16000 counts |
|
| accuracy drift according to temperature |
0.004 % of full scale/°C typical
0.007 % of full scale/°C maximum |
|
| isolation between channels and bus |
1780 V for 1 minute AC
|
|
| update time |
5 ms
|
|
| setting time |
1.6 ms to 5% of the final value
3.2 ms to +/-0.1% of the final value |
|
| fault type |
Open circuit 4...20 mA
|
|
| bus current requirement |
550 mA
|
|
| power dissipation in W |
5 W
|
|
| external power requirement |
6...30 V
|
|
| marking |
CE
|
|
| local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
| module format |
Standard
|
|
| product weight |
0.3 kg
|
| product certifications |
CUL
FM Class 1 Division 2 |
|
|---|---|---|
| standards |
CSA C22.2 No 142
UL 508 |
|
| resistance to electromagnetic fields |
10 V/m 80...2000 MHz conforming to IEC 801-3
|
|
| ambient air temperature for operation |
0...60 °C
|
|
| ambient air temperature for storage |
-40...85 °C
|
|
| relative humidity |
95 % without condensation
|
|
| operating altitude |
<= 5000 m
|
ANALOG OUT 8 CHAN CURRENT
| range of product | Modicon Quantum automation platform | |
|---|---|---|
| product or component type | Analogue output module |
| analogue output number | 8 | |
|---|---|---|
| addressing requirement | 8 output words | |
| loop voltage | 6...30 V DC | |
| voltage drop | 30 V 25 mA | |
| analogue output range |
0...20 mA 0...20000 counts 0...25 mA 0...25000 counts 4...20 mA 0...16000 counts 4...20 mA 0...4095 counts |
|
| absolute accuracy error | +/- 0.2 % of full scale at 25 °C | |
| linearity |
+/- 12 µA 4...20 mA 0...4095 counts +/- 4 µA 0...20 mA 0...20000 counts +/- 4 µA 0...25 mA 0...25000 counts +/- 4 µA 4...20 mA 0...16000 counts |
|
| accuracy drift according to temperature |
0.004 % of full scale/°C typical 0.007 % of full scale/°C maximum |
|
| isolation between channels and bus | 1780 V for 1 minute AC | |
| update time | 5 ms | |
| setting time |
1.6 ms to 5% of the final value 3.2 ms to +/-0.1% of the final value |
|
| fault type | Open circuit 4...20 mA | |
| bus current requirement | 550 mA | |
| power dissipation in W | 5 W | |
| external power requirement | 6...30 V | |
| marking | CE | |
| local signalling |
1 LED green bus communication is present (Active) 1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
| module format | Standard | |
| product weight | 0.3 kg |
| product certifications |
CUL FM Class 1 Division 2 |
|
|---|---|---|
| standards |
CSA C22.2 No 142 UL 508 |
|
| resistance to electromagnetic fields | 10 V/m 80...2000 MHz conforming to IEC 801-3 | |
| ambient air temperature for operation | 0...60 °C | |
| ambient air temperature for storage | -40...85 °C | |
| relative humidity | 95 % without condensation | |
| operating altitude | <= 5000 m |